Mod-2 wind turbine farm stability study / E. N. Hinrichsen and P. J. Nolan

Por: Colaborador(es): Tipo de material: TextoTextoIdioma: Inglés Series DOE/NASADetalles de publicación: Cleveland : National Aeronautics and Space Administration, 1980; Washington : United States Department of Energy, 1980Descripción: 164 p. : figurasTema(s): Recursos en línea:
Contenidos:
The dynamics of single and multiple 2.5 ME, Boeing MOD-2 wind turbine generators (WTGs) connected to utility power systems were investigated. The analysis was based on digital simulation. Both time response and frequency response methods were used. The dynamics of this type of WTG are characterized by two torsional modes, a low frequency 'shaft' mode below 1 Hz and an 'electrical' mode at 3-5 Hz. High turbine inertia and low torsional stiffness between turbine and generator are inherent features. Turbine control is based on electrical power, not turbine speed as in conventional utility turbine generators. Multi-machine dynamics differ very little from single machine dynamics.
Tipo de ítem: Libro
Valoración
    Valoración media: 0.0 (0 votos)
Existencias
Biblioteca actual Signatura topográfica Estado Fecha de vencimiento Código de barras
Koha Ingenieria 621.548 HIN Bloque 14 (Navegar estantería(Abre debajo)) Disponible 44645

Informe/número de patente NASA CR-165156

DOE/NASA/0134-1

The dynamics of single and multiple 2.5 ME, Boeing MOD-2 wind turbine generators (WTGs) connected to utility power systems were investigated. The analysis was based on digital simulation. Both time response and frequency response methods were used. The dynamics of this type of WTG are characterized by two torsional modes, a low frequency 'shaft' mode below 1 Hz and an 'electrical' mode at 3-5 Hz. High turbine inertia and low torsional stiffness between turbine and generator are inherent features. Turbine control is based on electrical power, not turbine speed as in conventional utility turbine generators. Multi-machine dynamics differ very little from single machine dynamics.

No hay comentarios en este titulo.

para colocar un comentario.

Haga clic en una imagen para verla en el visor de imágenes

Imagen de cubierta local
BIBLIOTECA CENTRAL
    Calle 115 y 47 - (CP1900) La Plata
    Tel: (0221) 423-6689  int 118 -
    Email: bibcentral@ing.unlp.edu.ar
    Horario de atención: Lunes a Viernes de 8 a 19 hs..
    +54 2215900419

Con tecnología Koha